GE LPS-D Instruction Manual page 339

Line protection system
Table of Contents

Advertisement

APPENDIX B
Table B–4: MODBUS MEMORY MAP: SETPOINTS
Register
DDE Item Name
Address
(Mnemonic)
R43000L
DATE_SET
R43002L
TIME_SET
R43026I
SYS_FREQUENCY
R43027I
PH_ROTATE
R43028I
TIME_SYNCH
R43029I
NUM_BKR
R43030I
NUM_TC
R43031I
NUM_MON
R43032I
DISP_VAL
R43033I
LANGUAGE
R43034I
COM_PORT1
R43035I
COM_PORT2
R43036I
COM_PORT3
R43037I
NUM_FAULTS
R43038I
SET_PREFAULT
R43039I
SPLIT_REC
R43040F
EXPONENT
R43042I
MAX_OP
R43043F
MAX_IXT
R43045F
IXT_PH_A
R43047F
IXT_PH_B
R43049F
IXT_PH_C
R43051I
NUM_OP
R43052I
NUM_OP_A
R43053I
NUM_OP_B
R43054I
NUM_OP_C
R43055I
CC_1
R43056I
CC_2
R43057I
CC_3
R43058I
CC_4
R43059I
CC_5
R43060I
CC_6
R43061I
CC_7
R43062I
CC_8
R43063I
CC_9
R43064I
CC_10
R43065I
CC_11
GE Power Management
(Sheet 1 of 27)
Contents
Units/Value/Range
Date
Time
SYSFREQ
Hertz; 50 or 60
PHASEROTATE
0 = ABC; 1 = ACB
TIMESYNCH
0 = internal; 1 = external
NUM_BKR
1, 2
NUM_TC
1, 2
NUM_MON
DISPLAYVAL
Language
0 = English; 1 = Spanish
COMPORT1
COMPORT2
COMPORT3
NUMFAULTS
7, 14, 28, 40
PREFAULT
1 to 8
SPLITREC
0 to 100%
EXPONENT
1.0 to 2.0
MAX_OP
0 to 9999
MAX_IXT
0 to 999.9M
IXTPHASEA
0 to 999.9M
IXTPHASEB
0 to 999.9M
IXTPHASEC
0 to 999.9M
NUM_OP
0 to 9999
NUM_OP_A
0 to 9999
NUM_OP_B
0 to 9999
NUM_OP_C
0 to 9999
CC_1
0 to 32
CC_2
0 to 32
CC_3
0 to 32
CC_4
0 to 32
CC_5
0 to 32
CC_6
0 to 32
CC_7
0 to 32
CC_8
0 to 32
CC_9
0 to 32
CC_10
0 to 32
CC_11
0 to 32
LPS-D Line Protection System
B.1 MEMORY MAPPING
B.1.4 SETPOINTS
R/W
Format
Code
R/W
F1
R/W
F2
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
F60
R/W
INT
R/W
F12
R/W
F13
R/W
F13
R/W
INT
R/W
INT
R/W
INT
R/W
Float
R/W
INT
R/W
Float
R/W
Float
R/W
Float
R/W
Float
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
B-
B
5

Advertisement

Table of Contents
loading