Table B–4: MODBUS MEMORY MAP: SETPOINTS
Register
DDE Item Name
Address
(Mnemonic)
R43985F
G3_REVREACH
R43987I
G3_OUTER
R43988I
G3_MIDDLE
R43989I
G3_INNER
R43990I
G3_TLOS1PU
R43991I
G3_TLOS1DO
R43992I
G3_TLOS2PU
R43993I
G3_TLOS3PU
R43994I
G3_TLOS4PU
R43995I
G3_RECLMODE
R43996I
G3_RECLOSETYPE
R43997I
G3_NUM_1P_AT
R43998F
G3_1PDELAY1
R44000F
G3_1PDELAY2
R44002F
G3_1PDELAY3
R44004F
G3_1PDELAY4
R44006I
G3_NUM_3P_AT
R44007F
G3_3PDELAY1
R44009F
G3_3PDELAY2
R44011F
G3_3PDELAY3
R44013F
G3_3PDELAY4
R44015F
G3_RESETTIME
R44017F
G3_DWELLTIME
R44019I
G3_HOLD
R44020I
G3_HOLDTIME
R44021I
G3_HOLDSENSE
R44022I
G3_SYNCHCHECK
R44023F
G3_CLOSEANG
R44025F
G3_SLIPFREQ
R44027I
G3_BUSLINE
R44028I
G3_SYNCHPHASE
R44029I
G3_SYNCHHOLD
R44030I
G3_SP1DELAY2
R44031I
G3_SP1DELAY3
R44032I
G3_SP1DELAY4
GE Power Management
(Sheet 19 of 27)
Contents
Units/Value/Range
0.1 to 75.0 Ω step 0.1 (5A)
REVREACH
0.5 to 375.0 Ω step 0.5 (1A)
OUTER
40 to 165° step 1
MIDDLE
40 to 165° step 1
INNER
40 to 165° step 1
TLOS1PU
1 to 100 msec. step 1
TLOS1DO
1 to 100 msec. step 1
TLOS2PU
1 to 100 msec. step 1
TLOS3PU
1 to 100 msec. step 1
TLOS4PU
1 to 100 msec. step 1
RECLMODE
0 = Off; 1 = None; 2 = Internal;
3 = External; 4 = Both
RECLOSETYPE
0 = 1POLE; 1 = 3 POLE;
2 = 1POLE3POLE
NUM_1P_AT
1, 2, 3, 4
1PDELAY1
0.1 to 300.0 sec. step 0.1
1PDELAY2
0.1 to 300.0 sec. step 0.1
1PDELAY3
0.1 to 300.0 sec. step 0.1
1PDELAY4
0.1 to 300.0 sec. step 0.1
NUM_3P_AT
1, 2, 3, 4
3PDELAY1
0.1 to 300.0 sec. step 0.1
3PDELAY2
0.1 to 300.0 sec. step 0.1
3PDELAY3
0.1 to 300.0 sec. step 0.1
3PDELAY4
0.1 to 300.0 sec. step 0.1
RESETTIME
0.1 to 300.0 sec. step 0.1
DWELLTIME
0.1 to 2.0 sec. step 0.1
HOLD
0 = No; 1 = Yes
HOLDTIME
1 to 1000 sec. step 1
HOLDSENSE
0 = CC; 1 = CO
SYNCHCHECK
0 = No, 1 = Yes
CLOSEANG
0 to 75° step 1
SLIPFREQ
0.1 to 5.0 Hz step 0.1
BUSLINE
0 = BUS; 1 = LINE
SYNCHPHASE
0 = VA; 1 = VB; 2 = VC
3 = VAB; 4 = VBC; 5 = VCA
SYNCHHOLD
1 to 100 sec. step 1
SP1DELAY2
1
SP1DELAY3
0 = No; 1 = Yes
SP1DELAYR
0 = No; 1 = Yes
LPS-D Line Protection System
B.1 MEMORY MAPPING
R/W
Format
Code
R/W
Float
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
Float
R/W
Float
R/W
Float
R/W
Float
R/W
INT
R/W
Float
R/W
Float
R/W
Float
R/W
Float
R/W
Float
R/W
Float
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
Float
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
B-