4 ACCEPTANCE/PERIODIC TESTS
4. Select
1. Display
and press the ENT key.
5. Check that the display has two rows filled completely with rectangles and press the ENT key. The display
changes to the last two rows filled with rectangles. When the display has been checked press the ACT key.
If any other key is pressed the display will not return to the LUI Test menu.
6. Use the ARROW keys to select
2. LEDs
and press the ENT key. The selected LED will change. Press ENT after verifying each LED state. When
the test is finished the LUI Test menu will be displayed.
7. Use the ARROW keys to select
3. Keyboard
and press ENT. A map of the key board will be displayed on the screen.
8. At this point the relay is in the keyboard test. Press every key on the keypad, except for the CLR key. As
you press each key, verify that the display indicates the key that was pressed. For example, pressing the
up arrow is indicated on the displayed by the up arrow flashing. The display corresponding to the other
keys is the legend that is on printed the key itself.
9. When all the keys have been checked, press the CLR key.
10. When the test is completed, press the END followed by the ENT key. Press the CLR key to clear the mes-
sage. This ends the Keypad/Display Interface Test.
This test checks all outputs of the relay. It is a convenient way to determine proper system connections and
verify the operation of all relay contacts, without having to apply currents and voltages to simulate faults. Pro-
tection can be enabled or disabled, as deemed necessary.
If this test is run remotely through ALPS-Link, then switch RM BRKR must be in the down
position to allow the outputs to operate. Refer to Section 8.4.1: HARDWARE SWITCHES for
details on changing the switch position. Note that the relay is shipped from the factory with
NOTE
the switch in the down position allowing the outputs to operate.
1. Connect the relay as shown in Figure 4–1: DIGITAL OUTPUT TEST CONNECTIONS on page 4–11.
2. Press the ACT key and enter the control level password.
3. Use the ARROW key to select
8. Digital Output Test
4. Press the ENT key. Before a contact is allowed to be tested, the display prompts
DISABLE PROTECT?
5. Press the 1/Y key followed by the ENT key to turn protection off. Protection remains off until the test mode
is ended (if desired, protection can be left enabled during the test).
6. Select the output to test by using the ARROW keys to scroll to the desired output, such as T1, and press
the ENT key. When the digital output is chosen, the selected relay output closes. Verify that the output
under test has closed, using an ohmmeter or other suitable device.
GE Power Management
LPS-D Line Protection System
4.2 GENERAL RELAY TESTS
4.2.3 T2 – DIGITAL OUTPUT TEST
4
4-
9