GE LPS-D Instruction Manual page 145

Line protection system
Table of Contents

Advertisement

2 CALCULATION OF SETTINGS
Table 2–10: PROTECTION SETTINGS DATA SHEET (Sheet 7 of 9)
No.
Mnemonic
1807
1PDELAY4
1808
NUM3P
1809
3PDELAY1
1810
3PDELAY2
1811
3PDELAY3
1812
3PDELAY4
1813
RESETTIME
1814
DWELLTIME
1815
HOLD
1816
HOLDTIME
1817
HOLDSENSE
1818
SYNCCHECK
1819
CLOSEANG
1820
SLIPFREQ
1821
BUSLINE
1822
SYNCPHASE
1823
SYNCHOLD
1824
SP1DELAY2
1825
SP1DELAY3
1826
SP1DELAY4
1827
SP3DELAY1
1828
SP3DELAY2
1829
SP3DELAY3
1830
SP3DELAY4
1831
SYN CM ANC LS
Setting value QUAD applies to LPS-D Revision B models only.
Setting is applicable to Revision B models only.
^
Setting is applicable to LPS-D models with three phase tripping only.
GE Power Management
Description
1 Pole Fourth Delay
Number of Attempts Following
3P Trip
3 Pole First Delay
3 Pole Second Delay
3 Pole Third Delay
3 Pole Fourth Delay
Reset Time
Contact Dwell Time
Inhibit Hold Select
Inhibit Hold Time
Contact Input Status
Synch Check Supervision
Closing Angle
Slip Frequency
Bus or Line Voltage
Voltage used by SYNCCHECK
SYNCCHECK Hold Time
Supervise 2nd 3P Reclose after
1P Trip
Supervise 3rd 3P Reclose after
1P Trip
Supervise 4th 3P Reclose after
1P Trip
Supervise 1st 3P Reclose after
3P Trip
Supervise 2nd 3P Reclose after
3P Trip
Supervise 3rd 3P Reclose after
3P Trip
Supervise 4th 3P Reclose after
3P Trip
Supervise Manual Close
LPS-D Line Protection System
2.5 REFERENCE TABLES
Range (5A)
Range (1A)
0.1 to 300 sec. step 0.1
1 to 4 step 1
0.1 to 300 sec. step 0.1
0.1 to 300 sec. step 0.1
0.1 to 300 sec. step 0.1
0.1 to 300 sec. step 0.1
0.1 to 300 sec. step 0.1
0.1 to 2 sec. step 0.1
YES, NO
1 to 1000 sec. step 1
CC, CO
YES, NO
0 to 75° step 1
0.1 to 5 Hz step 0.1
BUS, LINE
VA, VB, VC, VAB, VBC, VCA
1 to 100 sec. step 1
YES, NO
YES, NO
YES, NO
YES, NO
YES, NO
YES, NO
YES, NO
YES, NO
User Setting
2
2-
79