B.1 MEMORY MAPPING
Table B–4: MODBUS MEMORY MAP: SETPOINTS
Register
DDE Item Name
Address
(Mnemonic)
R44229I
G4_BYPASSTL3
R44230F
G4_I1PICKPU
B
R44232I
G4_REMOTEOPEN
R44233I
G4_TL20PICKUP
R44234I
G4_LINEOVERLD
R44235F
G4_LEVEL1PU
R44237F
G4_LEVEL2PU
R44239F
G4_LEVEL1TDLY
R44241F
G4_LEVEL2TDLY
R44243I
G4_PICKSCHEME
R44244I
G4_NUMRCVR
R44245I
G4_TRIPMODE
R44246I
G4_CARRSTART
R44247I
G4_WKINFTRIP
R44248I
G4_TL1PICKUP
R44249I
G4_TL4PICKUP
R44250I
G4_TL4DROPOUT
R44251I
G4_TL5PICKUP
R44252I
G4_TL5DROPOUT
R44253I
G4_TL6PICKUP
R44254I
G4_TL6DROPOUT
R44255I
G4_TL16PICKUP
R44256I
G4_TL24DROPOUT
R44257I
G4_TL25DROPOUT
R44258I
G4_TL26PICKUP
R44259I
G4_POSSEQANG
R44260I
G4_ZERSEQANG
R44261F
G4_ZLINE
R44263F
G4_ZEROSEQK0
R44265F
G4_LINELENGTH
R44267I
G4_LINEUNIT
R44268I
G4_CTRATIO
R44269I
G4_PTRATIO
B-
28
(Sheet 24 of 27)
Contents
Units/Value/Range
BYPASSTL3
0 = No; 1 = Yes
I1PICKUP
1.0 to 15.0 A step 0.1
0.2 to 3.0 A step 0.1
REMOTEOPEN
0 = No; 1 = Yes
TL20PICKUP
10 to 100 msec. step 1
LINEOVERLD
0 = No; 1 = Yes
LEVEL1PU
2.5 to 20.0 A step 0.1 (5A)
0.5 to 4.0 A step 0.1 (1A)
LEVEL2PU
5.0 to 40.0 A step 0.1 (5A)
1.0 to 8.0 A step 0.1 (1A)
LEVEL1TDLY
10 to 200 sec. step 1
LEVEL2TDLY
10 to 99 sec. step 1
PICKSCHEME
0 = STEPDST; 1 = PUTT;
2 = POTT1; 3 = POTT2;
4 = HYBRID
NUMRCVR
0, 1, 2
TRIPMODE
0 = 3POLE; 1 = 1POLE;
2 = 1POLEZ2
CARRSTART
0 = DIR; 1 = IPB; 2 = FD
WKINFTRIP
0 = No; 1= Yes
TL1PICKUP
1 to 200 msec. step 1
TL4PICKUP
0 to 50 msec. step 1
TL4DROPOUT
0 to 50 msec. step 1
TL5PICKUP
0 to 200 msec. step 1
TL5DROPOUT
0 to 200 msec. step 1
TL6PICKUP
0 to 200 msec. step 1
TL6DROPOUT
0 to 200 msec. step 1
TL16PICKUP
8 to 99 msec. step 1
TL24DROPOUT
30 to 500 msec. step 1
TL25DROPOUT
30 to 500 msec. step 1
TL26PICKUP
0 to 50 msec. step 1
POSSEQANG
25 to 90° step 1
ZERSEQANG
25 to 90° step 1
0.01 to 50 Ω step 0.01
ZLINE
0.05 to 250 Ω step 0.05
G4_ZEROSEQK0
1.0 to 7.0 step 0.1
LINELENGTH
0.0 to 500.0 step 0.1
LINEUNIT
0 = Miles, 1 = Km
CTRATIO
1 to 5000 step 1
PTRATIO
1 to 7000 step 1
LPS-D Line Protection System
APPENDIX B
R/W
Format
Code
R/W
INT
R/W
Float
R/W
INT
R/W
INT
R/W
INT
R/W
Float
R/W
Float
R/W
Float
R/W
Float
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
Float
R/W
Float
R/W
Float
R/W
INT
R/W
INT
R/W
INT