GE LPS-D Instruction Manual page 360

Line protection system
Table of Contents

Advertisement

B.1 MEMORY MAPPING
Table B–4: MODBUS MEMORY MAP: SETPOINTS
Register
DDE Item Name
Address
(Mnemonic)
R44133I
G4_Z3PCHARANG
R44134I
G4_Z3GRND
R44135F
G4_Z3GRDREACH
B
R44137I
G4_Z3GCHARACHAG
R44138F
G4_Z3P_TIME
R44140F
G4_Z3G_TIME
R44142I
G4_Z4PHASE
R44143F
G4_Z4PHREACH
R44145I
G4_Z4PCHRANG
R44146I
G4_Z4GRND
R44147F
G4_Z4GRDREACH
R44149I
G4_Z4GCHARANG
R44150I
G4_Z4DIRECTN
R44151I
G4_Z4TIMERS
R44152F
G4_Z4P_TIME
R44154F
G4_Z4G_TIME
R44156F
G4_IT_PICKUP
R44158F
G4_IB_PICKUP
R44160F
G4_IPT_PICKUP
R44162F
G4_IPB_PICKUP
R44164F
G4_IPBKFACTOR
R44166F
G4_NT_OFFSET
R44168I
G4_UNBALALARM
R44169I
G4_50
R44170I
G4_50_DIRCNL
R44171F
G4_50PICKUP
R44173F
G4_50PICKUPFF
R44175I
G4_50G
R44176I
G4_50G_DIRCNL
R44177F
G4_50GPICKUP
B-
26
(Sheet 22 of 27)
Contents
Units/Value/Range
Z3PCHARANG
90 to 120° step 5
Z3GRND
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.1 (5A)
Z3GRDREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z3CHARCHAG
90 to 120° step 5
Z3P_TIME
0.10 to 10.0 sec. step 0.01
Z3G_TIME
0.10 to 10.0 sec. step 0.01
Z4PHASE
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.01 (5A)
Z4PHREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z4PCHRANG
80 to 120° step 5
Z4GRND
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.01 (5A)
Z4GRDREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z4GCHARANG
80 to 120° step 5
Z4DIRECTN
0 = Forward; 1 = Reverse
Z4TIMERS
0 = No; 1 = Yes
Z4P_TIME
0.10 to 10.0 sec. step 0.01
Z4G_TIME
0.10 to 10.0 sec. step 0.01
IT_PICKUP
0.20 to 4.0 A step 0.01 (5A)
0.04 to 0.8 A step 0.01 (1A)
IB_PICKUP
0.20 to 4.0 A step 0.01 (5A)
0.04 to 0.8 A step 0.01 (1A)
IPT_PICKUP
0.50 to 5.0 A step 0.01 (5A)
0.1 to 1.0 A step 0.01 (1A)
IPB_PICKUP
0.25 to 3.75 A step 0.01 (5A)
0.05 to 0.75 A step 0.01 (1A)
IPBKFACTOR
0.0, 0.066
0.0 to 20.0 Ω step 0.01
NT_OFFSET
0.0 to 100 Ω step 0.01
UNBALALARM
0 = No; 1 = Yes
50
0 = No; 1 = Yes
50_DIRCNL
0 = No; 1 = Yes
50PICKUP
2.0 to 160.0 A step 0.1 (5A)
0.4 to 32.0 A step 0.1 (1A)
50PICKUPFF
2.0 to 160.0 A step 0.1 (5A)
0.4 to 32.0 A step 0.1 (1A)
50G
0 = No; 1 = Yes
50G_DIRCNL
0 = No; 1 = Yes
50GPICKUP
0.5 to 80.0 A step 0.1 (5A)
0.1 to 16.0 A step 0.1 (1A)
LPS-D Line Protection System
APPENDIX B
R/W
Format
Code
R/W
INT
R/W
INT
R/W
Float
R/W
INT
R/W
Float
R/W
Float
R/W
INT
R/W
Float
R/W
INT
R/W
INT
R/W
Float
R/W
INT
R/W
INT
R/W
INT
R/W
Float
R/W
Float
R/W
Float
R/W
Float
R/W
Float
R/W
Float
R/W
Float
R/W
Float
R/W
INT
R/W
INT
R/W
INT
R/W
Float
R/W
Float
R/W
INT
R/W
INT
R/W
Float
GE Power Management

Advertisement

Table of Contents
loading

Table of Contents