General Settings Data Sheet - GE LPS-D Instruction Manual

Line protection system
Table of Contents

Advertisement

2.5 REFERENCE TABLES
Table 2–11: GENERAL SETTINGS DATA SHEET (Sheet 1 of 3)
No.
Mnemonic
CONFIGURE
2
101
U N IT ID
102
SYSFREQ
103
PHASROTATE
104
TIMESYNCH
105
NUM_BKR
106
NUM_TC
107
NUM_MON
108
DISPLAYVAL
109
LANGUAGE
110
SYSIN1-4
COMMPORTS
201
C O M PO RT1
202
COMPORT2
203
COMPORT3
204
PROTOCOL1
205
PROTOCOL2
206
PROTOCOL3
Setting/value is applicable to LPS-D Three Phase Tripping models only.
Setting/value is applicable to LPS-D Single Phase Tripping models only.
2-
82
Description
Unit ID
System Frequency
Phase Rotation
Time Synch Source
Number of Breakers
Number of Trip Circuits
Number of Trip Circuit
Monitors
Value Display Mode
Language Option
System Inputs 1 to 4
Communications Port #1
Settings
Communications Port #2
Settings
Communications Port #3
Settings
Communications Port #1
Protocol
Communications Port #2
Protocol
Communications Port #3
Protocol
LPS-D Line Protection System
2 CALCULATION OF SETTINGS

2.5.5 GENERAL SETTINGS DATA SHEET

Range (5A & 1A)
Step
0000 to 9999
1
50 Hz, 60 Hz
N/A
ABC, ACB
N/A
INTERNAL, IRIG-B
N/A
1, 2
N/A
1, 2
N/A
a-f = 0 (on) or 1 (off)
(T6
T1)
format = abcdef
PRI, SEC
N/A
ENGLISH,
N/A
SPANISH
0000 to 1111 (bin)
1
0 to 15 (dec)
Baud Rate (xx),
xx = 03, 12, 24, 48,
Parity (y),
96, 19;
Stop Bits (z)
y = 1 (none), 1
format = xxyz
(odd), 2 (even)
z = 1, 2
Interface (i), Baud
i = 0 (RS232), 1
Rate (xx), Parity (y),
(RS485), xx = 03,
Stop Bits (z)
12, 24, 48, 96, 19; y
format = ixxyz
= 0 (none), 1 (odd),
2 (even); z = 1, 2
Interface (i), Baud
i = 0 (RS232), 1
Rate (xx), Parity (y),
(RS485), xx = 03,
Stop bits (z)
12, 24, 48, 96, 19; y
format = ixxyz
= 0 (none), 1 (odd),
2 (even); z = 1, 2
GE-MODEM,
N/A
ASCII, DNP 3.0
GE-MODEM,
N/A
ASCII, DNP 3.0
GE-MODEM,
N/A
ASCII, DNP 3.0
User Setting
GE Power Management

Advertisement