Right Resistive Blinder; Line Protection Schemes - GE LPS-D Instruction Manual

Line protection system
Table of Contents

Advertisement

1 PRODUCT DESCRIPTION
where ZD is the angle of "maximum torque" and is equal to 65°.
The characteristic timer angle will be fixed at 115°. That is, the function will operate when the input signals are
within ±65° of each other.
If the faulted phase voltage magnitude is too low (as for a close-in Zone 1 fault), the phase directional function
will not operate. This might also occur for a remote fault when the relay is located near a strong source. There-
fore, if the phase voltage is less than the minimum threshold voltage, the positive-sequence memory voltage
from the ground Mho functions is used in place of the phase voltage to polarize the directional function.
c) RIGHT RESISTIVE BLINDER
The right resistive blinder is a two input phase angle comparator. The input signals for the comparator are:
Iφ '· RB 1 - Vφ
Operate:
Iφ '· RB 1
Polarize:
where:
The magnitude of RB 1 (Right Blinder for Zone 1) is the point at which the characteristic inter-
sects the R axis. The range of adjustment will be 0.1 to 500.0 Ω in 0.1 Ω steps.
The angle of RB 1 is be fixed based on the positive sequence line angle, the zero sequence
line angle, and the K 0 factor. The angle is:
2 POSSEQANG
----------------------------------------------------------------------------------------------------- -
Iφ ' is the compensated phase current, ( I
The characteristic timer angle will be fixed at 90°. For the Zone 1 ground function, the operate and polarizing
signals are:
'· RB 1 – V
Phase A:
I
A
A
'· RB 1
I
A
'· RB 1 – V
Phase B:
I
B
B
'· RB 1
I
B
'· RB 1 – V
I
Phase C:
C
C
'· RB 1
I
C
The LPS-D provides four zones of distance protection with overcurrent backup functions. The LPS-D is a
highly flexible system: along with predefined protection schemes, it also has the ability to be programmed by
the user. The custom programmability of the LPS-D is discussed in the next section.
The LPS-D pilot protection schemes are as follows:
Permissive Underreach Transfer Trip (PUTT)
Permissive Overreach Transfer Trip (POTT1)
Permissive Overreach Transfer Trip with blocking functions (POTT2)
Blocking
Hybrid
In addition, each of the above schemes includes up to four zones of step distance backup with individual timers
for phase and ground zones.
GE Power Management
K 0 ZERSEQANG
+
K 0
2
+
- I
) + K
A
0
where:
' = ( I
I
- I
) + K
1· I
A
A
0
0
0
' = ( I
I
- I
) + K
1· I
B
B
0
0
0
' = ( I
I
- I
) + K
1· I
C
C
0
0
0
K
1 = | K
1| – (ZERSEQANG – POSSEQANG)
0
0
LPS-D Line Protection System
1.2 INTRODUCTION
1• I
0
0

1.2.5 LINE PROTECTION SCHEMES

1
1-
9

Advertisement

Table of Contents
loading

Table of Contents