GE LPS-D Instruction Manual page 142

Line protection system
Table of Contents

Advertisement

2.5 REFERENCE TABLES
Table 2–10: PROTECTION SETTINGS DATA SHEET (Sheet 4 of 9)
No.
Mnemonic
614
51GCURVE
615
51GTIMDIAL
616
DEFTIMDELY
2
617
51G_RESET
VOLTAGE
701
RATEDVOLTS
702
PHASEOVER
703
PHOVPICKUP
704
PHOVTMDLY
705 to 713 Not used
714
FUSEFAIL
BLK RECLOS
801
ALL_BELOW
802
OUTOFSTEP
803
ALL_3_Z2PH
804
50G_BLOCK
805
Z2TIMETRIP
806
Z3TIMETRIP
807
Z4TIMETRIP
808
Z1PHASTRIP
809
ANYZ2PHASE
810
CONFGTRIP
LINEPICKUP
901
LINEPICKUP
902
BYPASSTL3
903
I1PICKUP
REMOTEOPEN (THREE PHASE SYSTEMS ONLY)
1001
R EM O TEO PEN
Setting value QUAD applies to LPS-D Revision B models only.
Setting is applicable to Revision B models only.
^
Setting is applicable to LPS-D models with three phase tripping only.
2-
76
Description
51G Curve
51G Time Dial
Definite Time Delay
51G Reset Characteristic
Rated Per Unit Voltage
Select Phase Overvoltage
Phase Overvoltage Pickup
Phase Overvoltage Time Delay
Potential Fuse Failure Blocking
Block reclosing for any function
Block for Out of Step
Block for 3 phase faults
Block for 50G trip
Block for Z2 Time Delayed Trip
Block for Z3 Time Delayed Trip
Block for Z4 Time Delayed Trip
Block for any Z1 Phase Fault
Block for any Z2 Phase Fault
Block For Configurable Trip
Logic
Select Line Pickup
Bypass Line Pickup Time Delay
I1 Pickup
Select Remote Open Detector
LPS-D Line Protection System
2 CALCULATION OF SETTINGS
Range (5A)
Range (1A)
INV, V-INV, E-INV, CUSTOM, DEFT
0.5 to 10.0 step 0.1
0.5 to 30.0 sec. step 0.1
FAST, EM
100, 105,110,115, 120 volts
NO, YES
0.0 to 1.4 p.u. volts step 0.01
0.0 to 10.0 sec. step 0.01
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
NO, YES
1.0 to 15.0 amps
0.2 to 3.0 amps
step 0.1
step 0.1
NO, YES
User Setting