11/2006
300865
Axis %1 drive %2 measurement of DC link voltage not possible
Parameters:
%1 = NC axis number
%2 = Drive number
Definitions:
If the fixed voltage MD 1161: $MD_FIXED_LINK_VOLTAGE(DC link fixed voltage) = 0, no DC link
measurement is possible because the hardware version is wrong.
Reaction:
Interface signals are set.
Alarm display.
Remedy:
Please inform the authorized personnel/service department. Enter a value greater than zero in the
machine data MD 1161: $MD_FIXED_LINK_VOLTAGE (DC link fixed voltage), or order a new
hardware version of the control module.
Program
Alarm display showing cause of alarm disappears. No further operator action necessary.
Continuation:
300875
Axis %1 drive %2 fixed link voltage of axes differ
Parameters:
%1 = NC axis number
%2 = Drive number
Definitions:
An unequal fixed voltage MD1161: $MD_FIXED_LINK_VOLTAGE (DC link fixed voltage) has been
found for axes of a drive module. Since a fixed voltage <> 0 replaces the measured DC link voltage
value, but the DC link voltage value is measured only once for all axes of a drive module, the fixed
voltage must be identical on all module axes before it is accepted.
Reaction:
Interface signals are set.
Alarm display.
Remedy:
Please inform the authorized personnel/service department. Set the same fixed voltage (MD 1161) on
all module axes.
Program
Alarm display showing cause of alarm disappears. No further operator action necessary.
Continuation:
300888
Axis %1 drive %2 parameterization error in current control adaption
Parameters:
%1 = NC axis number
%2 = Drive number
Definitions:
The upper current limit in MD 1181: $MD_CURRCTRL_ADAPT_CURRENT_2 (upper adaption
current limit) is less than the lower current limit in MD 1180: $MD_CURRCTRL_ADAPT_CURRENT_1
(lower adaption current limit).
Reaction:
Interface signals are set.
Alarm display.
Remedy:
Modify MD 1181: $MD_CURRCTRL_ADAPT_CURRENT_2 (upper adaption current limit) and MD
1180: $MD_CURRCTRL_ADAPT_CURRENT_1 (lower adaption current limit).
Program
Alarm display showing cause of alarm disappears. No further operator action necessary.
Continuation:
© Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
Overview of Alarms
SIMODRIVE alarms
2-765