Huawei FusionModule 1000B Maintenance Manual page 133

Air-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
Figure 6-42 Access controller
1.
2.
3.
4.
Remove the lower screws and then the upper ones.
5.
Step 3 Take out a new access controller, and set the device address for the access controller by
following instructions in the management system initial configuration table.
Step 4 Install the new access controller and reconnect the terminal blocks and network cable.
Install terminals on the left and right of the access controller based on the mapping between cable labels
and the silk screens on the access controller.
Step 5 Secure the access controller.
Step 6 Switch on the power circuit breaker of access controller, and configure the access card
permission by referring to the NetEco commissioning guide.
Step 7 Verify that the access controller works properly.
The access controller is working properly if the container door can be opened from outside using an
access card and from inside using the exit button, and the door opening operation is logged in the
monitoring system.
Issue 02 (2017-01-10)
Remove the terminals on the right side of the access controller.
Remove the terminals on the left side of the access controller.
Remove the network cable on the top of the access controller.
Use a Phillips screwdriver to remove the four screws that fasten the access controller.
Push the access controller upwards to remove it.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 Parts Replacement
125

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusionmodule 1000

Table of Contents