Step 7 Configure the ECC500 collector based on the management system initial configuration table
for the solution in use.
----End
Follow-up Procedure
Dispose of the removed ECC500 collector that is confirmed faulty.

6.3.12 Replacing an RH2288 Server

Prerequisites
Impact on the System
The operation of the RH2288 system or devices connected to the server may be interrupted.
Preparations
Tools: Phillips screwdriver, small-sized flat-head screwdriver, ESD gloves, marker
Materials: spare RH2288 server
Documents: documents delivered with the RH2288 server, management system initial
configuration table, monitoring device layout diagram
Skill requirement: weak-current engineer
Procedure
Step 1 Press and hold the power switch on the front panel of the RH2288 server to power off the
server, and disconnect the power plug.
Step 2 Mark cables and ports on the RH2288 server using a marker.
Step 3 Remove all cables connected to the RH2288 server.
Step 4 Remove the faulty RH2288 server using a Phillips screwdriver and install a new RH2288
server.
Issue 02 (2017-01-10)
If the power indicator on the main control module of the ECC500 collector is on and the ECC500
collector is communicating properly with the management system, the ECC500 collector is working
properly.
An RH2288 server needs to be replaced.
A spare RH2288 server of the same model is available and functional.
For the diagrams and tables, see the initial configuration parameter manual for the solution in use.
For details about how to replace devices inside the RH2288 server, see documents delivered with the
RH2288 server.