FusionModule1000B Air-Cooled IT Solution
Maintenance Guide

5.15 UPS5000-E Alarms

Fault
Category
UPS5000-
E alarms
Issue 02 (2017-01-10)
Alar
Symptom
m
Sever
ity
Major
The rectifier cannot
work, and the bus
voltage is not
boosted.
Major
The buzzer buzzes,
the Fault indicator is
on, the inverter is
faulty, and the UPS
transfers to bypass
mode.
Major
When the mains is
normal, the UPS
works in bypass
mode and does not
transfer to inverter
mode.
For other UPS5000-E alarms, see documents delivered with the product.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Troubleshooting
Cause
The mains
Check whether the mains
voltage exceeds
voltage exceeds the
the upper
thresholds. If yes,
threshold 278 V
contact the electric
or is less than
power company.
the lower
threshold 80 V.
PFC soft-startup
Contact Huawei
fails.
technical support.
The power
module is
faulty.
Output overload
Reduce loads or
or short-circuit
troubleshoot the
exists.
short-circuited load.
The UPS5000-E
Install more air
inverter
conditioners or
temperature
ventilation devices to
exceeds the
ensure normal
upper threshold.
temperatures inside the
equipment room.
The power
Contact Huawei
module is
technical support.
faulty.
The UPS is set
Set the UPS working
to ECO mode.
mode correctly.
The number of
Reset the bypass transfer
bypass transfer
times on the LCD.
times reaches
the upper
threshold.
5 Alarms and Faults
68