Huawei FusionModule 1000B Maintenance Manual page 97

Air-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
Figure 6-10 Removing the air filter
Step 4 Remove air filters at the middle and bottom in the same way.
Step 5 Install a new air filter.
Do not touch the pressure tube during the replacement, and verify that the pressure tube is
correctly connected after the replacement.
Install air filters as instructed by the labels to avoid reverse installation.
Step 6 Switch on the upstream circuit breaker, and tap Start on the home screen after the controller
is powered on.
Step 7 Choose Maint > Performance Maint on the home screen and clear the air filter running
time.
----End
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 Parts Replacement