FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
----End
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.

7.14 Emergency Operations for a LOCAL FIRE Alarm (CE)

Prerequisites
The management system reports a LOCAL FIRE alarm.
Procedure
Step 1 Locate the alarm area based on the alarm information.
Step 2 Check the internal situation in the video surveillance system.
Step 3 Check whether extinguishant has been released.
Step 4 If no extinguishant is released, take necessary tools and communications devices, arrive at the
site as soon as possible, and press the manual gas release button on the extinguishant control
panel to start releasing extinguishant.
Issue 02 (2017-01-10)
The following LOCAL FIRE emergency operations are for reference only.
If you find a LOCAL FIRE alarm when working inside a container, determine whether to
extinguish the fire or leave the area immediately based on the actual situation and contact
the personnel on duty or fire engineer.
If the video surveillance system indicates that everything is normal, go to
If onsite fire is confirmed, go to
If extinguishant is being released, contact the local maintenance engineer or Huawei
technical support to recharge the extinguishant after the fire has been extinguished.
If no extinguishant is released, check the situation onsite, and contact the fire engineer.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Step
3.
7 Emergency Operations
Step
5.
195