Fault
Category
Issue 02 (2017-01-10)
Alar
Symptom
m
Sever
ity
Major
The compressor
generates a loud
noise.
Major
An indoor fan does
not work.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Troubleshooting
Cause
manual.
The sheet metal
Remove the sheet metal
for securing the
and check whether the
compressor
abnormality disappears.
during
transportation is
not removed.
The compressor
Troubleshoot by
starts and stops
following instructions in
at short
Comp HP switch, and
intervals.
check whether the
abnormality disappears.
The compressor
Contact Huawei
technical support.
suffers from
liquid strike.
A fan alarm is
Check whether an alarm
generated.
is generated. If yes,
handle the alarm by
referring to the alarm
reference list.
The fan does not
Choose Running >
need to work.
Status on the controller
home screen and check
the indoor fan control
status. If the control
status is 0%, the fan does
not need to work, and
there is no fault. If the
control status is greater
than 0%, the fan is faulty
and needs to be rectified.
The switch of
Turn on the switch, and
the indoor fan is
check whether the
not turned on.
abnormality disappears.
Power supply to
Check the power supply
the indoor fan is
to the indoor fan.
abnormal.
Remove the terminals of
the fan, and check
whether the voltage
between the 0 V and 48
V terminals is 48 V using
a multimeter. If the
voltage differs too much,
the power supply is
abnormal.
5 Alarms and Faults