Fault
Category

5.13 PDU8000 MDU Alarms

Fault
Category
PDU8000
MDU
alarms
Issue 02 (2017-01-10)
Alar
Symptom
m
Sever
ity
Alar
Symptom
m
Sever
ity
Major
The user interface
does not display
branch currents.
Major
The user interface
fails to display the
circuit breaker status.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Troubleshooting
Cause
closed contact).
Possible
Troubleshooting
Cause
The monitoring
Check that cables are
board
properly connected.
communications
cable or the
secondary cable
to the
corresponding
branch current
transformer is
not properly
connected.
The monitoring
If the monitoring board
board or current
or current transformer is
transformer is
faulty, replace the faulty
faulty.
monitoring board or
current transformer.
The
Check that the Boolean
communications
value collection module
cable of the
is properly connected to
Boolean value
the branch Boolean value
collection
signal cable.
module or the
corresponding
branch Boolean
value signal
cable is not
properly
connected.
The Boolean
Check the Boolean value
value collection
collection module and
module or
auxiliary switch contact.
auxiliary switch
If the collection module
contact is faulty.
or auxiliary contact is
faulty, replace it.
5 Alarms and Faults