Emergency Operations For A Double Fire Alarm (Standard) - Huawei FusionModule 1000B Maintenance Manual

Air-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.
7.12 Emergency Operations for a Double Fire Alarm
(Standard)
Prerequisites
The management system reports a double fire alarm.
Procedure
Step 1 Locate the alarm or alarm area in the management system.
Step 2 Check the internal situation in the video surveillance system.
Step 3 Check whether extinguishant has been released.
Step 4 Arrive at the site with necessary tools and communications devices as soon as possible, open
the external fire control box, and press the EMERGENT RELEASE on the fire alarm
control panel.
Issue 02 (2017-01-10)
The following double fire alarm emergency operations are for reference only.
If a double fire alarm is generated, determine whether to extinguish the fire or leave the
area immediately based on the actual situation and contact the personnel on duty or fire
engineer.
If the video surveillance system indicates that everything is normal, go to
If onsite fire is confirmed, go to
If extinguishant is being released, contact the local maintenance engineer or Huawei
technical support to recharge the extinguishant after the fire has been extinguished.
If no extinguishant is released, check the situation onsite, and contact the fire engineer.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Step
3.
7 Emergency Operations
Step
5.
191

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusionmodule 1000

Table of Contents