Mains Outage; Communication Failure Alarms - Huawei FusionModule 1000B Maintenance Manual

Air-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Air-Cooled IT Solution
Maintenance Guide

5.10 Mains Outage

Fault
Category
Mains
outage

5.11 Communication Failure Alarms

Fault
Category
PD510
communic
ation
failure
MDU
communic
ation
failure
Issue 02 (2017-01-10)
Alar
Symptom
m
Sever
ity
Major
The
FusionModule1000
is power off.
The DG cannot be
started.
A circuit breaker
cannot be operated,
or an action does not
take effect.
Alar
Symptom
m
Sever
ity
Major
Real-time
monitoring cannot be
performed.
Major
Real-time
monitoring cannot be
performed.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Troubleshooting
Cause
The mains
Switch to another mains
supply is cut
or DG.
off.
The dry contact
Check the dry contact of
of the electricity
the electricity meter.
meter is faulty.
The DG startup
Contact Huawei
failed.
technical support.
The PDC circuit
Contact Huawei
breaker is
technical support.
faulty.
Possible
Troubleshooting
Cause
Cables are not
Verify the cable
properly
connections.
connected.
Powered on the power
distribution equipment
where the electricity
meter is installed again.
The device is
Replace by following
faulty.
instructions in
Replacing a
Cables are not
Verify the cable
properly
connections.
connected.
Powered on the power
distribution equipment
where the MDU is
installed again.
The device is
Replace by following
faulty.
instructions in
5 Alarms and Faults
6.1.1
PD510.
6.1.2
64