FusionModule1000B Air-Cooled IT Solution
Maintenance Guide

5.16 35 kW Air-Cooled Precision Air Conditioner Alarms

Fault
Category
35 kW
air-cooled
precision
air
conditione
r alarms
Issue 02 (2017-01-10)
Alar
Symptom
m
Sever
ity
Major
There is an abnormal
noise during
operation.
Major
The compressor does
not work.
Major
The compressor
exhaust temperature
is too high.
Major
The indoor fan fails
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Troubleshooting
Cause
The compressor,
Check and secure loose
fan, or pipes are
parts.
loose.
The high
Check the high pressure
pressure switch
switch.
is triggered.
The circuit
Check the main circuit
breaker, fuse, or
breaker, compressor
cable is
circuit breaker, fuses,
disconnected.
and cables.
The compressor
Check whether the motor
motor is
is damaged and needs
damaged.
replacing.
The compressor
Check for the
does not need to
requirement status on the
start.
LCD.
The refrigerant
Clean up foreign matter
loop or
from the refrigerant loop.
component is
blocked.
The outdoor
Properly install the
unit is not
outdoor unit. Do not
properly
expose it to direct
installed.
sunshine, and verify that
the distances meet
requirements in the
installation manual.
Air enters the
Exhaust air and repair
refrigerant loop.
the pipeline.
Heat dissipation
Clean the condenser fins.
is poor because
the condenser is
dirty or blocked.
The outdoor fan
Check whether the
fails.
outdoor fan is working
properly.
The refrigerant
Fill more refrigerant.
is insufficient.
The main circuit
Check the status of
5 Alarms and Faults
69