FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Tab
Date and
Time Settings
Teamwork
Settings
Issue 03 (2021-04-20)
Parameter
Date format
Date settings
Time zone
Time
Teamwork group No.
System address
Networking mode
Teamwork function
Number of systems in
this group
Number of running
systems in this group
Teamwork power limit
function
Copyright © Huawei Digital Power Technologies Co., Ltd.
7 Power-On Commissioning
Description
Specifies the date format.
Specifies the date.
Specifies the time zone.
Specifies the time.
Specifies the planned teamwork group
number. This parameter should be the
same for all units in the same
teamwork group.
Specifies the planned unit address. The
addresses of units in the same
teamwork group must be unique.
Specifies the networking mode for
teamwork control. The networking
mode selected on the screen must
match the actual networking mode.
Otherwise, the teamwork function is
unavailable.
Specifies whether to enable the
teamwork function. Set this parameter
based on onsite heat load distribution.
● Disable: A unit operates
independently.
● Enable: A unit operates in team
with other units.
Specifies the total number of units in
this group. The value is an integer
ranging from 1 to 32.
NOTE
This parameter is displayed after
Teamwork function is set to Enable.
Specifies the number of running units
in this group. The value is an integer
ranging from 1 to the value of
Number of systems in this group.
NOTE
This parameter is displayed after
Teamwork function is set to Enable.
Limits the power of the teamwork
group.
NOTE
This parameter is displayed after
Teamwork function is set to Enable.