Figure 13-12 Alarm details
Step 3 Tap Fault Diagnosis_Repair to view the diagnosis report. Rectify the faults by
following instructions in the diagnosis report.
----End
Follow-up Procedure
To query historical alarms, choose Common Function > Query Hist Alarms on
the home screen or choose Alarms > Query Hist Alarms on the home screen.

13.2.11 How Do I Clear Component Runtime?

Context
Performance value clearance can only be performed after component
maintenance. Otherwise, the component may run overtime and weaken the
performance of the unit.
Procedure
Step 1 On the home screen, choose Maint > Performance Maint.
Step 2 Tap Clear in the row of a performance parameter to clear the runtime.
----End

13.2.12 How Do I Calibrate a T/H Sensor?

Context
Calibrate a sensor if the displayed temperature or humidity values on the sensor
deviate from the actual values. For example, if the return air temperature
measured by other precise temperature measurement units at the return air