13.2.16 How Do I Set the Balance of Water and Electricity
Consumption?
Procedure
Step 1 On the home screen, choose Settings > System Settings > System Control and
set Balance of water and electricity consumption based on the actual situation.
Figure 13-16 Setting parameters
----End

13.2.17 How Do I Set Alarm Parameters?

Prerequisites
Before setting the alarm parameters, get familiar with the coupling relationship
among each parameter.
Configurations of temperature and humidity alarms and main board settings for
the air-cooled devices should comply with the following coupling relationships:
Issue 03 (2021-04-20)
NO TE
You can set LCD password complexity check to Enable or Disable and set the complexity
of the password.
If a password with low complexity is set, the system will display a message indicating that
the password complexity is low and asking you to set a new one. Examples of low
complexity passwords: H#uawei123, Password and openasadminAdmin23@#.
NO TE
Energy saving effect of different modes: Power saving mode > Normal water saving mode >
Extreme water saving mode.
Select Power saving mode in areas with abundant water resources.
Select Normal water saving mode in areas with balanced water and electricity resources.
Select Extreme water saving mode in areas with water resources shortage.
Select Customized mode based on the setting of Wet mode startup temperature.
Power supply underfrequency alarm threshold < Power supply overfrequency
alarm threshold