Installing Pipes - Huawei FusionCol8000-E24 User Manual

Modular indirect evaporative cooling system
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Figure 5-7 Installing an air duct
(1) Indoor return air duct
(end)
----End

5.4.5 Installing Pipes

The designed height of the water trap must meet the requirements specified in
Figure
Figure 5-8 Designed height of the water trap
Issue 03 (2021-04-20)
NO TE
● The air duct must be wrapped with thermal insulation foam, and the thickness of the
thermal insulation foam must be greater than or equal to 3 cm.
● The joint between the air duct and the unit should be sealed to prevent air leakage.
Generally, the sealing cotton is pressed inside the flange of the air duct or sealant is
applied to the flange after installation.
4-10.
NO TE
It is recommended that the height of segment B be as low as possible.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 System Installation (FDC Scenario)
(2) Indoor supply air duct
(3) Indoor return air duct
(side)
78

Advertisement