Huawei FusionCol8000-E24 User Manual page 39

Modular indirect evaporative cooling system
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Item
Sensible heat
ratio
System
dimensions (H x
W x D)
Installation
scenario
Power system
Air filter level on
the indoor air
return side (EN
779)
Air filter level on
the outdoor air
intake side (EN
779)
Fan type
Air volume
Net weight
Operating weight
1
Test conditions: The outdoor dry and wet bulb temperatures are 35°C and 27°C
respectively; the indoor return and supply air temperatures are 38°C at 25% RH
and 25°C at 50% RH respectively; the external residual pressures of the indoor
and outdoor units are 150 Pa and 100 Pa respectively. If the indoor return air
temperature is lower than 38°C, the cooling capacity of the equipment is
derated.
Table 3-4 Compressor cooling specifications
Item
Compressor type
Number of compressors
Throttling device
Refrigerant
Issue 03 (2021-04-20)
FDC Scenario
100%
4150 mm x 2438 mm x 6058 mm
FDC
380–415 V AC, 3-phase, 50 Hz/60 Hz
G4
G3
EC
Indoor: 55,000 m
Outdoor: 50,000 m
11,000 kg
11,500 kg
Copyright © Huawei Digital Power Technologies Co., Ltd.
3
/h
3
/h
Specifications
Variable-frequency scroll compressor
3
EEV
R410A