FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Figure 12-25 Removing a fan
Step 7 Remove the six screws that secure the fan to the fan support to separate the fan
from the fan support.
Figure 12-26 Removing the fan support
Step 8 Install the new fan on the fan support, push the fan and fan support, insert the
fan terminal, and secure the terminal using cable ties.
Step 9 Install the maintenance door for the fan sealing plate.
Step 10 Power on the unit, choose Maint > Wizard Startup on the home screen, and
commission the exhaust fan to check that it works properly before you exit.
Step 11 Choose Maint > Performance Maint on the home screen and clear the total
runtime of the exhaust fan.
Step 12 Tap Start on the home screen. Ensure that the unit is running normally without
any alarms.