12.23 Replacing an SPD

Prerequisites
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the unit
switch in the PDF.
Exercise caution because the unit is still energized after it is shut down on the
home screen of the display module.
Step 2 Open the door of the electric control box.
Step 3 Pry the clip ring of the faulty SPD using a flat-head screwdriver, and remove the
faulty SPD.
Figure 12-48 Removing an SPD
Issue 03 (2021-04-20)
A surge protective device (SPD) needs to be replaced.
A spare SPD of the same model is available and functional.
Tools: Phillips screwdriver, flat-head screwdriver