FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Parameter
Teamwork power limit
function
Teamwork spray water
renewal function
Teamwork spray drain
function
Teamwork systems
draining spray water
together
Teamwork total system
power limit
Step 3 Perform
group.
Step 4 On the home screen of the display module of any unit in the teamwork group, tap
the group is displayed.
Figure 7-5 Teamwork topology
Issue 03 (2021-04-20)
Step 1
and
Step 2
. If the teamwork networking succeeds, the teamwork topology of the unit in
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
After the teamwork power limit function is enabled,
you can set Teamwork total system power limit.
The master unit controls all units in the group to
ensure that the total power of units does not exceed
the value of Teamwork total system power limit.
● Enable: Only one unit in the group is allowed to
renew water at a time.
● Disable: Each unit in the group renews water
based on their own water renewal logic. Multiple
units can renew water at the same time.
● Enable: The units whose quantity is specified by
Teamwork systems draining spray water
together in the group are allowed to drain water
at the same time.
● Disable: Each unit in the group drains water based
on their own water renewal logic. Multiple units
can drain water at the same time.
This parameter is used together with Teamwork
spray drainage function to limit the number of units
that are allowed to drain water at the same time in a
group.
NOTE
This parameter is displayed after Teamwork spray drain
function is set to Enable.
Specifies the total power of the teamwork group.
to configure teamwork control for all units in the
7 Power-On Commissioning
121