Huawei FusionCol8000-E24 User Manual page 131

Modular indirect evaporative cooling system
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
No.
1
2
3
4
5
6
----End
Follow-up Procedure
After you have completed the teamwork settings, check that the teamwork
networking is successful by performing the following steps:
Issue 03 (2021-04-20)
Item
On/Off
01/02/03...
Active/Standby
M/S
Frame: green/non-
green
Background color:
red/bright gray
NO TE
If the teamwork networking is successful, the teamwork icon is green. If the teamwork
networking fails, the teamwork icon is red. If the teamwork networking is disabled, the
teamwork icon is gray.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Note
● On: The device is started.
● Off: The device is shut down.
Indicates the device address. The smallest
address is for the master unit and the rest are
for slave units.
If the master unit is offline, the online device
with the smallest address is selected to be the
new master.
Active: An active unit properly responds to
control requirements.
Standby: A standby unit responds to control
requirements only if an active unit is faulty
(critical alarm, shutdown, or offline) or the
active unit cannot meet cooling requirements.
● M: master unit
● S: slave unit
A blue icon indicates that the unit is operating,
and a gray icon indicates that the unit is idle.
● A green frame indicates the current unit, as
shown in
.
● Devices without a green frame indicate
other devices in the teamwork group.
● Red indicates that the unit has generated a
critical alarm, as shown in
● Bright gray indicates that the device is
operating without any critical alarms.
7 Power-On Commissioning
.
122

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusioncol8000-e240

Table of Contents