Huawei FusionCol8000-E24 User Manual page 117

Modular indirect evaporative cooling system
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Tab
Issue 03 (2021-04-20)
Parameter
DO_1
Copyright © Huawei Digital Power Technologies Co., Ltd.
7 Power-On Commissioning
Description
● If this parameter is set to Smoke &
Water only, DO_1 acts according to
DO_1 action when a smoke or
water overflow alarm is generated.
● If this parameter is set to Critical
alarm, DO_1 acts according to
DO_1 action when a critical alarm
is generated.
● If this parameter is set to Major
alarm, DO_1 acts according to
DO_1 action when a major alarm is
generated.
● If this parameter is set to Alarm,
DO_1 acts according to DO_1
action when a critical alarm, major
alarm, or warning is generated.
● If this parameter is set to Startup
status, DO_1 acts according to
DO_1 action when the unit is
started.
● If this parameter is set to No, no
alarm is generated when DO_1 is
disconnected.