FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Step 3 Remove the side sealing plate from the fan to be maintained.
Step 4 Cut the cable tie that binds the cable connected to the faulty fan, and remove the
fan terminal.
Step 5 Pull out the two fans horizontally by holding the fan assembly handles.
1.
2.
Figure 12-24 Removing the fan assembly
Step 6 Unscrew the fan support and take out the fan.
Issue 03 (2021-04-20)
NO TE
When maintaining the fan, stand on the operation platform.
If the first fan needs to be replaced, remove the bolts between the first and
second fans, and replace the fan.
If the second fan needs to be replaced, the latch is stuck when you pull out
the second fan. Press the latch and pull out the fan horizontally.
NO TE
Two persons are required to pull out the fan.
Copyright © Huawei Digital Power Technologies Co., Ltd.
12 Component Replacement