Huawei FusionCol8000-E24 User Manual page 202

Modular indirect evaporative cooling system
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Figure 12-43 Removing a liquid level sensor
(1) Water tank cover
Step 4 Replace the liquid level sensor at the bottom of the precooling module.
Issue 03 (2021-04-20)
Loosen the nut on the liquid level sensor using a wrench and take out the
sensor from the water tank.
Remove the adjustable side panel and water barrier of the air supply fan.
Cut off the cable tie that secures the liquid level sensor cable, and remove the
interconnection terminal.
Remove the fastener from the liquid level sensor at the bottom of the
precooling module.
Loosen the nut on the liquid level sensor using a wrench and take out the
sensor.