FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Figure 4-5 Hoisting a unit
Step 6 Secure the unit to the concrete platforms using four right angle brackets.
1.
2.
Figure 4-6 Securing the unit to the concrete platforms
Step 7 Install the equipotential ground cable or ground lug.
Issue 03 (2021-04-20)
Secure the right angle brackets to the unit using common bolts.
Secure the right angle brackets to the concrete platforms using expansion
bolts.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 System Installation (Building Scenario)
43