Product Specifications; Technical Specifications; System Specifications (Building Scenario) - Huawei FusionCol8000-E24 User Manual

Modular indirect evaporative cooling system
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual

3.1 Technical Specifications

3.1.1 System Specifications (Building Scenario)

Table 3-1 System specifications
Item
Maximum power
Maximum
current
Total cooling
capacity
Sensible cooling
capacity
Sensible heat
ratio
System
dimensions (H x
W x D)
Installation
scenario
Power system
Air filter level on
the indoor air
return side (EN
779)
Issue 03 (2021-04-20)
3
Building Scenario
78.5 kW (default power)
140 A (default current)
240 kW
240 kW
100%
3600 mm x 2438 mm x 4700 mm
Indoor
380–415 V AC, 3-phase, 50 Hz/60 Hz
G4