FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Tab
Issue 03 (2021-04-20)
Parameter
DO_2
Floor water overflow
alarm action
Copyright © Huawei Digital Power Technologies Co., Ltd.
7 Power-On Commissioning
Description
● If this parameter is set to Smoke &
Water only, DO_2 acts according to
DO_2 action when a smoke or
water overflow alarm is generated.
● If this parameter is set to Critical
alarm, DO_2 acts according to
DO_2 action when a critical alarm
is generated.
● If this parameter is set to Major
alarm, DO_2 acts according to
DO_2 action when a major alarm is
generated.
● If this parameter is set to Alarm,
DO_2 acts according to DO_2
action when a critical alarm, major
alarm, or warning is generated.
● If this parameter is set to Startup
status, DO_2 acts according to
DO_2 action when the unit is
started.
● If this parameter is set to No, no
alarm is generated when DO_2 is
disconnected.
● If this parameter is set to Power
abnormal, DO_2 acts according to
DO_2 action when a power
exception alarm is generated.
Set the action of the device if there is
water overflow on the floor based on
the actual scenario.
● Shutdown: The device shuts down
when a floor water overflow alarm
is generated.
● Inactivity: The device runs as usual
when a floor water overflow alarm
is generated.
● Only indoor fan running: Only the
indoor fan runs when a floor water
overflow alarm is generated.
● Humidifier stopped: Only the
humidifier is stopped when a floor
water overflow alarm is generated.
● Comp & Humid stopped: The
compressor and humidifier are
stopped when a floor water
overflow alarm is generated.