FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Figure 5-11 Drainpipe routing (bottom pipe routing)
(1) Drainage manifold
Step 1 Install the water refill pipe.
1.
2.
3.
Step 2 Install the drainpipe.
Figure 5-13 Installing the drainpipe
Issue 03 (2021-04-20)
NO TE
● The specifications of the drainage manifold must be greater than or equal to DN50.
● As shown in the preceding figure, the water trap should be installed on the drainage
manifold.
● The horizontal gradient of the branch drainpipe along the water flow direction is not
less than 1%, and the horizontal gradient of the main drainpipe is not less than 3‰.
Remove the sheet metal from the water refill pipe.
Install the water refill pipe.
Install the sheet metal for the water refill pipe.
Figure 5-12 Installing a water refill pipe
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 System Installation (FDC Scenario)
(2) Water trap
80