Context
Be careful when configuring alarm parameters. Only professional maintenance
personnel can change alarm settings.
Procedure
Step 1 On the home screen, choose Settings > Alarm Settings > T/H Sensor.
Figure 13-17 Setting alarm parameters
Step 2 Tap the value next to the Threshold column of the Return air high temperature
alarm.
Issue 03 (2021-04-20)
Standby power underfrequency alarm threshold < Standby power
overfrequency alarm threshold
Supply air high temperature alarm threshold + 5°C ≤ Return air high
temperature alarm threshold
Supply air high temperature alarm threshold + 5°C ≤ Hot aisle high
temperature alarm threshold
Cold aisle high temperature alarm threshold + 5°C ≤ Hot aisle high
temperature alarm threshold
Cold aisle high temperature alarm threshold + 5°C ≤ Return air high
temperature alarm threshold
Supply air low temperature alarm threshold + 5°C ≤ Return air low
temperature alarm threshold
This section describes how to set an alarm threshold.
All alarm thresholds are configured in the same way. This section describes
how to set the threshold of Return air high temperature alarm for the T/H
sensor.
If you need to change alarm settings, log in as user Admin.