Chapter 6 Power cables connection
Single phase UPS units, 5594-8KX and 5594-9KX
This section applies to the following Lenovo UPS units:
RT8kVA 6U Rack or Tower UPS (200-240V
•
RT11kVA 6U Rack or Tower UPS (200-240V
•
Common input sources connection
Separate input source connection
74
), 5594-8KX
AC
AC
1. Make sure the jumper is connected.
2. Insert the Normal AC cable through the cable gland.
3. Connect the three cables to the Normal AC source
terminal blocks.
4. Insert the Output cable through the cable gland.
5. Connect the three cables to the Output terminal blocks.
6. Put back and secure the terminal blocks cover with the
screw.
7. Tighten the cable glands.
Note: The L1 to L1 connection is needed if a secondary external
bypass utility connection is not used.
1. Remove the jumper.
2. Insert the Normal AC cable through the cable gland.
3. Connect the three cables to the Normal AC source
terminal blocks.
4. Insert the Bypass AC cable through the cable gland.
5. Connect the three cables to the Bypass AC source
terminal blocks.
6. Insert the Output cable through the cable gland.
7. Connect the three cables to the Output terminal blocks.
8. Put back and secure the terminal blocks cover with the
screws.
9. Tighten the cable glands.
), 5594-9KX
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG