Lenovo 5594-8KX User, Installation And Maintenance Manual page 284

6u rack or tower ups rt 8.0 kva and rt 11.0 kva and maintenance bypass
Hide thumbs Also See for 5594-8KX:
Table of Contents

Advertisement

Appendix A. Specifications
Overview - 11 kVA UPS units (continued)
Specification
Electrical input
Input voltage
Input frequency
Frequency slew rate
Max input amperage
Input connector
Input line cord
Electrical output
Output voltage settings
Output frequency
Output power capacity
Output connectors
Batteries
Battery type
Battery management
Battery replacement
External battery support
Typical backup times
256
RT11kVA 6U Rack or Tower
UPS (200-240VAC)
200 - 240 V
,
AC
1-Phase
50 – 60 Hz
1 Hz / s
0.5 Hz / s HE Mode
50 A
Hardwired terminal block
Onsite wiring required
200/208/220/230/240 V
50/60 Hz
200-208 V AC: 10000 VA/9000 W
220 V AC: 11000 VA/9900 W
230-240 V AC: 11000 VA/10000 W
4x IEC 320-C19 (16 A) (on the MBP)
Valve Regulated Lead Acid (VRLA): Maintenance-free, sealed,
leak-proof
ABM technology or temperature-compensated charging method
(user selectable), automatic battery test and deep discharge
protection, and automatic recognition of external battery units
Hot-swap standard and extended battery modules
Up to 4 (PN 55949BX)
See the
Backup / Run time Tables
RT11kVA 6U 3:1 Phase Rack
or Tower UPS (380-415VAC)
380 - 415 V
3-Phase
50 – 60 Hz
1 Hz / s
0.5 Hz / s HE Mode
50 A
AC
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
,
AC

Advertisement

Table of Contents
loading

This manual is also suitable for:

5594-8px5594-9kx5594-9px

Table of Contents