Lenovo 5594-8KX User, Installation And Maintenance Manual page 118

6u rack or tower ups rt 8.0 kva and rt 11.0 kva and maintenance bypass
Hide thumbs Also See for 5594-8KX:
Table of Contents

Advertisement

Chapter 6 Power cables connection
With common Normal and Bypass AC source
1. Connect the 2 integrated power cables
colour coding on the cables and the UPS I/O cover (blue for UPS Input / red for UPS
Output), see
to check the UPS terminal blocks connection
2. Connect the MBP detection cable
3. Slide the MBP I/O cover
blocks
4. Insert the Normal AC source cable through the cable gland
5. Connect the wires to the Normal AC source (Input) terminal blocks (do not remove the
Input Bypass AC jumper
6. Insert the Output cable through the cable gland
7. Connect the wires to the Output terminal blocks
8. Tighten the cable glands
9. Slide back and secure the MBP I/O cover
90
Figure 31 Principal connections - Maintenance Bypass Panel, UPS Power Module
after removing the 5 screws, to access to MBP terminal
and the UPS Input Bypass jumper inside the UPS I/O cover
to the UPS I/O terminal blocks, following
to the specific UPS connector, see
with the 5 screws
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
Figure 2, item
10.