Chapter 3 Overview
User settings (continued)
Submenu
Battery settings
Restart battery level
(continued)
Battery charge mode
External battery
Deep discharge protection [Yes] [No]
Extended Battery Modules (EBMs)
An Extended Battery Module allows to extend the run-time or backup-time of the UPS unit.
Up to four EBMs can be connected to the UPS.
Note: The base UPS unit is shipped with one EBM. A maxmium of four additional EBMs can be
attached to the UPS power module.
Part number
55949BX
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
Available settings
[0%] ... [100%]
If set, automatic restart will occur only
when percentage of battery charge is
reached.
Note: Network Management Card
settings supersede the LCD settings!
[ABM cycling] [Constant charge]
[Auto detection] [Manual EBM set.]
[Manual battery set.] [No battery]
If set to Yes, the UPS automatically
prevents battery pack from deep
discharge by adapting end of back-up
time voltage threshold. Warranty void if
set to No.
Description
Additional Extended Battery Module
Default settings
[0%]
[ABM cycling]
[Auto detection]
Using standard
EBM, UPS detects
automatically the
number of EBM
connected
[Yes]
21