Chapter 5 Installation
Preparing the EBM for rack mounting
Note: This step requires two people.
The Extended Battery Module is very heavy. To ease its rack mounting, you can remove the
battery packs from the EBM by following these steps.
Step 1. Remove the centre section of the front bezel.
Step 2. Remove the four captive screws to open the front bezel.
Step 3. Remove the three screws to pull out the metal protection cover of the battery pack.
Step 4. Pull out the plastic handle of the left and right battery packs, and slide the packs out slowly on to a flat
and stable surface. Use two hands to support the battery packs. Set them aside for reinstalling after
that the EBM is rack mounted.
Step 5. Mount the EBM in the rack.
52
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG