Lenovo 5594-8KX User, Installation And Maintenance Manual page 285

6u rack or tower ups rt 8.0 kva and rt 11.0 kva and maintenance bypass
Hide thumbs Also See for 5594-8KX:
Table of Contents

Advertisement

Appendix A. Specifications
Overview - 11 kVA UPS units (continued)
Specification
Communications and management
USB port (Type B)
RS-232 serial port (RJ-45)
10/100 Mbps Ethernet port
(RJ-45)
*)
Environmental monitoring
Management software
Control panel
LED indicators
Remote On/Off and Power Off Remote On/Off and Remote Power Off terminal block connectors
Attention! The communication ports are exclusive!
*)
It is not possible to use two or all three simultaneously!
Physical specifications
RT8kVA and RT11kVA 6U UPS 130 mm (5.1 in) x
Extended Battery Module
Operating Environment
The RT8kVA and RT11kVA 6U Rack or Tower UPS units are supported in the following
environments:
Temperature (operation): 0 - 40 °C (32 - 104 °F), with linear derating for altitude
Relative humidity: 0 - 95%
Maximum altitude (operation): 3,000 m (9,843 ft)
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
RT11kVA 6U Rack or Tower
UPS (200-240VAC)
Yes
*)
Yes
*)
Yes (on the Network Management Card)
Optional with Environmental Monitoring Probe, 46M4113
(connects to the Network Management Card)
UPS Power Manager and UPS Power Protector
Intelligent 5-button graphical LCD
Online, On Battery, Bypass, and Fault
Dimensions (H x W x D) Weight (kg / lb)
441 mm (17.4 in) x
700 mm (27.6 in)
130 mm (5.1 in) x
441 mm (17.4 in) x
680 mm (26.8 in)
RT11kVA 6U 3:1 Phase Rack
or Tower UPS (380-415VAC)
Yes
Yes
8kVA 1-phase (55948KX): 19 kg (42 lb)
8kVA 3-phase (55948PX): 23 kg (51 lb)
11kVA 1-phase (55949KX): 21 kg (46 lb)
11kVA 3-phase (55949PX): 23 kg (51 lb)
65 kg (143 lb)
257

Advertisement

Table of Contents
loading

This manual is also suitable for:

5594-8px5594-9kx5594-9px

Table of Contents