Chapter 10 UPS maintenance
Step 5.
On the MBP, unlock the Normal AC source switch
and set them to the (on) position.
Step 6.
Wait for the UPS to start functioning.
The display panel illuminates and displays the standby symbol:
Step 7.
Press the power ( X ) button to turn on the UPS.
The UPS goes into online mode:
Step 8.
Select
Control
The UPS goes into internal bypass mode:
136
→
Go to Bypass
and the Bypass AC source switch
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
,