Appendix A. Specifications
Recommended upstream protection (normal upstream source)
UPS power rating
8000 VA
11000 VA
The use of an RCD with any of these UPS units is strongly discouraged due to the high leak currents.
(*)
For futher information see the section
Recommended upstream protection (bypass AC source)
UPS power rating
8000 VA
11000 VA
Front and back view
The following figures are the front and back view of the 8000VA and 11000 VA UPS units
with EBM and MBP, 4xIEC 320 C19 outlets.
266
Upstream CB
D curve – 50 A
D curve – 70 A
Leak current information
Upstream CB
D curve – 50 A
D curve – 70 A
Upstream RCD
D curve – 50 A, 420 mA
D curve – 70 A, 420 mA
in
Chapter
12.
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
(*)