Chapter 7 Maintenance Bypass Panel Operations
After opening the UPS I/O terminal blocks cover, check if hazardous voltage is no longer
present on UPS terminal blocks by using an electrical safety tester.
Disconnect the MBP power power cables, and the MBP detection cable, see
and
Figure 14 (item 6)
On each MBP power cables just disconnected from the UPS, link the wires together (line
and neutral wires linked to ground wire).
Replace the UPS
Hazardous voltage and lost load risk: do not manipulate the MBP manual Bypass switch without
UPS connected to the MBP power cables.
only in case of Bypass AC source option connected.
(*)
100
for details.
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG