Chapter 6 Power cables connection
With separate Normal and Bypass AC source
1. Slide the MBP Bypass Input cover
2. Punch the UPS Bypass Input knockout of the MBP Bypass Input cover
provided cable gland inside.
3. Insert a power cable (refer to 3.5 for cable cross-section) through the cable gland of the
MBP Bypass Input cover
4. Connect the wires to the "Input BP" terminal blocks of the MBP Bypass Input cover
5. Tighten the cable gland.
6. Slide back and secure the MBP Bypass Input cover
7. Connect the 2 integrated power cables
power cable to the UPS I/O terminal blocks, following colour coding on the cables and
the UPS I/O cover (blue for UPS Input / red for UPS Output / yellow for UPS Input
Bypass) – see
Module
to check the UPS terminal blocks connection (do not forget to also remove the
Input Bypass AC jumper on UPS).
8. Connect the MBP detection cable
9. Slide the MBP I/O cover
blocks
10.
Remove the Input Bypass AC jumper
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
(cable not provided in the packaging).
Figure 31 Principal connections - Maintenance Bypass Panel, UPS Power
after removing the 5 screws, to access to MBP terminal
after removing the 3 screws.
with the 3 screws.
and the previously installed Bypass Input
to the specific UPS connector, see
and insert a
.
Figure 2, item
10.
91