System Installation
Table 11-2.
PDU to PCM Connections
1-------------1------------T------------1
I
wi re Color
1
PDU at TB 1
I
P CN at TB 3
I
I
I
I
I
1-------------1------------1------------1
I
Black
I
1
I
6
I
I
Red
I
3
I
7
I
I
Orange
1
5
I
8
I
I
Wh i
te
I
12
I
9
I
IGreen-Yellow
I
Earth Bus
I
Earth Bus
I
1
I
I
I
Table 11-3. PDU Ac Service Str ip Wi ring
---------------r------------r------------------
Service Str ip
Identity
Wire Color
PCU Terminal
11SV
230V
(CCE-22)
11-3. Power Control Unit
Black
White
Green-Yellow
Brown
Blue
Green-Yellow
TB 1 Term inal 8
TBl Term inal 12
Ear th Bus-Bar
TBl Term inal
9
TBl Term inal
6
Ear th Bus-Bar
If the system does not contain a PCU,
proceed to paragraph 11-4.
Otherwise, perform the following instructions.
a.
Remove the large and small panels
(seen from the rear of the
cabinets) from the PCU.
Save all hardware.
b.
Verify that
jumpers have been installed correctly on
TBI as
listed within figure 11-2.
c.
Have an
electrician perform
this step.
Connect primary
ac
power cable
wires to the PCU line filter
terminals as shown
in figure 11-3.
Then, replace the panels removed in step a.
d.
Remove all ac power plugs from all ac power service strips in
the equipment bays.
e.
Use the PCu-to-PCU/PCM
Interconnecting Cable furnished
with
each PCU to connect Jl of the PCU to
J
2 of the PCM in the CPU
Bay (par a 11-4).
Figure 11-4 shows the wir ing of the cable.
f.
Leave the access plates off and proceed to paragraph 11-4.
11-5