HP 3000 III Series Manual page 383

Table of Contents

Advertisement

System Installation
GROUND
LUG
PRIMARY
SIDE COVER
PLATE
ADDITIONAL STRAPPING OPTIONS
ISOLATION TRANSFORMER
(VIEWED FROM RIGHT SIDE OF
ELECTRONIC MAINFRAME. ACCESS
PANEL REMOVED FOR CLARITY:
TYPICAL 208 VOLT STRAPPING EXAMPLE)
WIRE
WIRE
VOLTAGE
BLACK
JUMPER
RED
200V
PIN 1
PIN 2
PIN 5
PIN 6
208V
PIN 1
PIN 3
PIN 5
PIN 6
220V
PIN 1
PIN 3
PIN 5
PIN 7
230V
PIN 1
PIN 4
PIN 5
PIN 7
240V
PIN 1
PIN 4
PIN 5
PIN 8
Figure 11-6.
Isola tion
Tr
ansformer Strapping Otions
that meets
the voltage
requirements of table
11-5
and the
isolation transformer
must always be strapped for the
RATED
vol tage.
f.
Ensure that all terminal block connections are tight and that
no loose strands of wire are
protruding
from
the
terminal
block.