Toshiba GRE110 Instruction Manual page 124

Overcurrent protection relay
Table of Contents

Advertisement

O f
F /
O n
S E 4 -
D I
R
F W D /
R E V /
S E 4 -
2 F
N A /
B l
o
c
k
Z P E N
O f
f
/
O n
<SE1EN>, <SE2EN>
• Enter 1(=On) to enable the SEF1 or SEF2 and press the ENTER key. If disabling the SEF1,
enter 0(=Off) and press the ENTER key.
<SE∗-DIR>
The settings are for model 820 series,to set SEF∗ directional characteristic, do the following.
Enter 0(=FWD) or 1(=REV) or 2(=NON) and press the ENTER key.<MSE1C>, <MSE2C>
To set the Inverse Curve Type, do the following.
• If [MSE1] or [MSE2] is 1(=IEC), enter 0(=NI) or 1(=VI) or 2(=EI) or 3(=LTI) and press the
ENTER key.
• If [MSE1] or [MSE2] is 2(=IEEE), enter 0(=MI) or 1(=VI) or 2(=EI) and press the ENTER
key.
• If [MSE1] or [MSE2] is 3(=US), enter 0(=CO2) or 1(=CO8) and press the ENTER key.
<SE1R>, <SE2R>
To set the Reset Characteristic, do the following.
• If [MSE1] or [MSE2] is 2(=IEEE) or 3(=US), enter 0(=DEF) or 1(=DEP) and press the
ENTER key.
<SE1S2>
To set the Stage 2 Timer Enable, do the following.
• Enter 1(=On) to enable the SE1S2 and press the ENTER key. If disabling the SE1S2, enter
0(=Off) and press the ENTER key.
<SE3EN, SE4EN>
• Enter 1(=On) to enable the SEF3 and press the ENTER key. If disabling the SEF3, enter
0(=Off) and press the ENTER key. The SEF4 is the same.
<SE1-2F, SE2-2F, SE3-2F, SE4-2F>
• Enter 1(=Block) to block the SE1, SE2, SE3 and SE4 against the inrush current, and press the
ENTER key.
0
Display at model 820 series.
N O N
0
0
Display at model 820 series.
 123 